Universiti Teknologi Malaysia Institutional Repository

Hierarchical control strategy for a three-phase 4-wire microgrid under unbalanced and nonlinear load conditions

Naderipour, Amirreza and Abdul-Malek, Zulkurnain and Ramachandaramurthy, Vigna K. and Kalam, Akhtar and Miveh, Mohammad Reza (2019) Hierarchical control strategy for a three-phase 4-wire microgrid under unbalanced and nonlinear load conditions. ISA Transactions, 94 . pp. 352-369. ISSN 0019-0578

Full text not available from this repository.

Official URL: http://dx.doi.org/10.1016/j.isatra.2019.04.025

Abstract

This paper proposes an improved hierarchical control strategy consists of a primary and a secondary layer for a three-phase 4-wire microgrid under unbalanced and nonlinear load conditions. The primary layer is comprised of a multi-loop control strategy to provide balanced output voltages, a harmonic compensator to reduce the total harmonic distortion (THD), and a droop-based scheme to achieve an accurate power sharing. At the secondary control layer, a reactive power compensator and a frequency restoration loop are designed to improve the accuracy of reactive power sharing and to restore the frequency deviation, respectively. Simulation studies and practical performance are carried out using the DIgSILENT Power Factory software and laboratory testing, to verify the effectiveness of the control strategy in both islanded and grid-connected mode. Zero reactive power sharing error and zero frequency steady-state error have given this control strategy an edge over the conventional control scheme. Furthermore, the proposed scheme presented outstanding voltage control performance, such as fast transient response and low voltage THD. The superiority of the proposed control strategy over the conventional filter-based control scheme is confirmed by the 2 line cycles decrease in the transient response. Additionally, the voltage THDs in islanded mode are reduced from above 5.1% to lower than 2.7% with the proposed control strategy under nonlinear load conditions. The current THD is also reduced from above 21% to lower than 2.4% in the connection point of the microgrid with the offered control scheme in the grid-connected mode.

Item Type:Article
Uncontrolled Keywords:microgrid, nonlinear load, voltage control
Subjects:T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions:Electrical Engineering
ID Code:88385
Deposited By: Yanti Mohd Shah
Deposited On:15 Dec 2020 00:02
Last Modified:15 Dec 2020 00:02

Repository Staff Only: item control page