Shaban, M. and Salam, M. A. and Ang, S. P. and Sidik, M. A. B. and Buntat, Z. and Voon, W. (2016) Assessing induced sheath voltage in multi-circuit cables: revising the methodology. In: 2nd IEEE Conference on Energy Conversion, CENCON 2015, 19 - 20 Okt 2015, Johor Bahru, Malaysia.
Full text not available from this repository.
Official URL: https://www.scopus.com/inward/record.uri?eid=2-s2....
Abstract
Flow of current in a cable conductor generates a magnetic field which could induce current flow in the metallic cable shield or sheath. This paper examines induced voltage calculation in multi-circuit of the cables with the hope of proposing new methodology for induced sheath voltage computation in metallic shield of a single-core power cable operating in a triple circuit. This study considers a few examples to demonstrate the method of examining the induced voltage in single, double and triple-circuits. The calculated values for induced voltages were 0.079 V/m, 0.074 V/m and 0.068 V/m for triple, double and single circuit. It is found that induced sheath voltage increased with the increase in number of the cables.
Item Type: | Conference or Workshop Item (Paper) |
---|---|
Uncontrolled Keywords: | Cable magnetic field, Induced sheath voltage, Multi circuit, Single circuit, Single core power cable |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering |
Divisions: | Electrical Engineering |
ID Code: | 73422 |
Deposited By: | Mohd Zulaihi Zainudin |
Deposited On: | 23 Nov 2017 01:37 |
Last Modified: | 23 Nov 2017 01:37 |