Universiti Teknologi Malaysia Institutional Repository

Partial Discharge characterization based on leakage current pulses waveform for contaminated glass insulator string

Othman, Nordiana Azlin and Mohamed Piah, Mohamed Afendi and Adzis, Zuraimy (2015) Partial Discharge characterization based on leakage current pulses waveform for contaminated glass insulator string. In: The 1st. ICRIL-International Conference on Innovation in Science and Technology (IICIST 2015), 20 April, 2015, Kuala Lumpur, Malaysia.

[img]
Preview
PDF
2MB

Abstract

Partial discharge (PD) is an electrical discharge event that does not completely bridges the electrodes in the insulation systems under applied field. Although PD does not cause immediate breakdown of the insulation, it may affect the insulation performance in the long term due to repetition of PD events. The occurrence of PD causes leakage current (LC) to flow, thus an attempt to characterize PD based on LC pulses waveform is presented in this paper. Results show that PD can be characterized (according to their occurrence with respect to the AC supply) as follows: corona discharge occurring in lightly contaminated insulators, surface discharge occurring in medium contaminated insulators and finally internal discharge occurring in heavily contaminated insulators. The ability to distinguish the type of PDs from the LC waveform could be used to monitor and predict the condition of the insulator. The outcome can be incorporated in a conditioning monitoring system.

Item Type:Conference or Workshop Item (Paper)
Uncontrolled Keywords:partial discharge, leakage current
Subjects:T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions:Electrical Engineering
ID Code:61883
Deposited By: Widya Wahid
Deposited On:30 Apr 2017 07:42
Last Modified:31 Jul 2017 07:39

Repository Staff Only: item control page