Universiti Teknologi Malaysia Institutional Repository

Sea Salts Contamination Pattern on High Voltage Insulators In Littoral Region of Peninsular Malaysia

Ahmad, Ahmad S. and Ahmad, Hussein and Salam, Md. Abdus (1999) Sea Salts Contamination Pattern on High Voltage Insulators In Littoral Region of Peninsular Malaysia. Electrical Insulation and Dielectric Phenomena, 1999 Annual Report Conference on , 2 . pp. 670-673.

[img] PDF
240kB

Abstract

This paper describes series results of experiments conducted at Paka Thermal Power Station, which is located near the East Coast of Peninsular Malaysia. More than 12 samples of typical cap-and-pin glass insulators that are commonly installed on electrical power transmission lines are used in the experimentation. Three types of insulator topology are employed, single units, suspension-type and tension-type. These un-energized insulators are allowed to be exposed to 3-4 months duration of sea salts contamination. Equivalent salt deposit density (ESDD) measurement is conducted to measure insulator's contamination level. It was found that salt accumulation on suspension type insulator is much heavier than the tension type. Also the direction of inward coming winds has some influence on the salt deposition to the insulator surfaces. Experiments showed that ESDD increases linearly with an increase in time of exposure. This work will help in the establishment of maintenance policies especially in the months of monsoon when generally many utilities thought that during these months maintenance of insulators is not necessary

Item Type:Article
Subjects:T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions:Electrical Engineering
ID Code:1964
Deposited By: Dr Zaharuddin Mohamed
Deposited On:19 Mar 2007 05:08
Last Modified:01 Jun 2010 02:59

Repository Staff Only: item control page