Investigation of partial discharges in non-woody kenaf based pressboard under influence of moisture

Kurnia, Rizda Fitri and Mat Saman, Norhafezaidi and Ahmad, Mohd. Hafizi and Nawawi, Zainuddin and Azrin, Nur Azalia and Talib, Mohd. Aizam (2022) Investigation of partial discharges in non-woody kenaf based pressboard under influence of moisture. Indonesian Journal of Electrical Engineering and Computer Science, 28 (3). pp. 1309-1321. ISSN 2502-4752

[img]
Preview
PDF
1MB

Official URL: http://dx.doi.org/10.11591/ijeecs.v28.i3.pp1309-13...

Abstract

The most crucial parts that decide the transformer s lifetime are the solid insulation of the power transformer, especially the pressboard and kraft paper. The life of the insulation is significantly influenced by the presence of water in the insulation. This paper presents a study on partial discharge (PD) on the existing normal pressboard (NP) and the newly developed Kenaf-polypropylene pressboard (KPP). Also, the moisture content of the pressboard varied between 0%, 1%, and 3% by the percentage weight of different methods. After the initiation of PD, the surface deterioration analysis was performed by using scanning electron microscopy (SEM). The results from the study revealed that KPP shows superior performance in mitigating PD. At 0%, 1% and 3% moisture contents, KPP showed 89%, 83% and 25% reductions in average PD magnitude, respectively. Overall, the kenaf composite pressboard has better PD resistance, which is one of the things to think about when insulating a transformer.

Item Type:Article
Uncontrolled Keywords:kenaf-polypropylene pressboard, moisture, normal pressboard
Subjects:T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions:Electrical Engineering
ID Code:100423
Deposited By: Narimah Nawil
Deposited On:14 Apr 2023 01:29
Last Modified:14 Apr 2023 01:29