Toh, Chuen Ling and Tan, Chee Wei (2021) DC traction power substation using eighteen-pulse rectifier transformer system. International Journal of Power Electronics and Drive Systems, 12 (4). pp. 2284-2394. ISSN 2088-8694
|
PDF
640kB |
Official URL: http://dx.doi.org/10.11591/ijpeds.v12.i4.pp2284-22...
Abstract
Twelve-pulse rectification system had been widely integrated in today’s DC traction power sub-station (DC-TPSS). This configuration had successfully mitigated low order harmonic distortion. As some research findings had confirmed that the DC voltage and current ripple factors may further minimize by increasing the number of rectification pulses to 18, 24, or 36. This paper had presented a simulation study to investigate the prospect of implementing an eighteen-pulse rectification system in a DC-TPSS. The theory of phase-shifting transformer used to produce an 18-pulse rectifier is presented with simulation verification. Simulation result shows that 3.69% of grid current distortion index is recorded without installing any filters. In addition, the DC voltage and current ripple may also be further reduced for about 30% compared to a conventional twelve-pulse rectification system.
Item Type: | Article |
---|---|
Uncontrolled Keywords: | DC traction power substation, Harmonic mitigation, Multipulse rectifier, Phase-shifting transformer, Total harmonic distortion |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering |
Divisions: | Electrical Engineering |
ID Code: | 97652 |
Deposited By: | Widya Wahid |
Deposited On: | 25 Oct 2022 10:17 |
Last Modified: | 25 Oct 2022 10:17 |