Voltage stability analysis: Case study in Madura 150 kV transmission system

Rosyadi, F. U. and Aripriharta, A. and Rosmin, N. and Fadlika, I. (2020) Voltage stability analysis: Case study in Madura 150 kV transmission system. In: 2019 International Conference on Renewable Energy, ICORE 2019, 9 - 10 August 2019, Malang, Indonesia.

[img]
Preview
PDF
545kB

Official URL: http://dx.doi.org/10.1088/1742-6596/1595/1/012015

Abstract

Voltage stability problem during the operation of the power system cause serious failures in the power system, so that making the development of stability analysis an important necessity. In this study, the data taken were Gilitimur, Bangkalan, Sampang, Pamekasan and Sumenep bus obtained from PT. PLN (Persero) UP2B East Java Madura 150 kV system area. In March 2019 there was a large voltage drop on the Sumenep bus so that the voltage was 133 kV. In power systems, the system voltage must be maintained within the limits (+ 5%) and (-10%) of the nominal voltage. Based on these regulations, the voltage condition on the Sumenep load bus experiences a voltage drop of 17 kV or >10% so that the voltage drop has exceeded the allowable voltage standard, whereas on other buses in Madura the region has also experienced a voltage drop that is almost close to the standard limit as in the Sampang bus has a voltage drop of 137 kV. To predict the voltage stability of the system in Madura, it can be done with a voltage stability analysis study using the Q-V Sensivity Analysis method. This analysis can be useful to determine which buses are prioritized for maintenance. In the Q-V Sensivity Analysis it is assumed that the bus voltage and load is absolute, when the value of Jacobian reduction (JR) is negative, indicating that the bus condition is unstable. In the analysis of the Sumenep bus the negative value is -0.015 while the other buses are positive namely the Gilitimur bus = 1.225, Bangkalan bus = 0.502, Sampang bus = 0.448 and Pamekasan bus = 0.287, so it can be concluded that the 150 kV Madura transmission system has unstable buses is the Sumenep bus.

Item Type:Conference or Workshop Item (Paper)
Uncontrolled Keywords:Voltage stability, Madura 150 kV system
Subjects:T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions:Electrical Engineering
ID Code:93063
Deposited By: Widya Wahid
Deposited On:07 Nov 2021 05:59
Last Modified:07 Nov 2021 05:59

Repository Staff Only: item control page