The leakage current components as a diagnostic tool to estimate contamination level on high voltage insulators

Salem, A. A. and Abd. Rahman, R. and Al Gailani, S. A. and Kamarudin, M. S. and Ahmad, H. and Salam, Z. (2020) The leakage current components as a diagnostic tool to estimate contamination level on high voltage insulators. IEEE Access, 8 . pp. 92514-92528. ISSN 2169-3536

[img]
Preview
PDF
2MB

Official URL: http://www.dx.doi.org/10.1109/ACCESS.2020.2993630

Abstract

The current paper presents an alternative and innovative technique to predict the severity of pollution of high voltage insulator using a higher harmonics component with up to the 7th component of leakage current. The leakage current was measured using a current transformer and a shunt resistor. Next, laboratory tests were conducted on glass and porcelain insulators with artificial pollution under salt-fog pollution state which is further represented by three levels, namely light, medium, and high contamination. In this case, the formulation of a new severity of harmonic index refers to a ratio of the sum of 5th and 7th to the 3rd harmonic component. More importantly, the new index managed to provide more accurate results when used as a diagnostic tool for the levels of pollution, compared to the ratio of the total harmonic distortion (THD) to the number of odd harmonics components (n) as the boundaries. In this case, the insulators were found to be in a clean and normal condition when the K(5+7)/3 value was greater than 3%. Contrastingly, the insulators were in an extreme condition when the K(5+7)/3 was lower than 3%. Nevertheless, there is a high probability of a flashover in glass and porcelain insulators if the K(5+7)/3 value is less than 2%. The present study shows the possibility of utilizing the value of strange harmonics up to the 7th component of leakage current as the parameter for the monitoring of leakage current in overhead insulators in the presence of contamination. Overall, it can be concluded that the 3rd, 5th, and 7th harmonics details extracted from the leakage current act as a good indicator for the level of contamination.

Item Type:Article
Uncontrolled Keywords:fast fourier transform, harmonic components, leakage current
Subjects:T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions:Electrical Engineering
ID Code:87971
Deposited By: Narimah Nawil
Deposited On:30 Nov 2020 13:44
Last Modified:30 Nov 2020 13:44

Repository Staff Only: item control page