Universiti Teknologi Malaysia Institutional Repository

Characterization of arcing fault in underground distribution cable

Chan, W.K and Mohd Zin , A.A. and Majid, M. S. and Ahmad, Hussein and Muda, Z. and Lo, Kueiming Lun (2003) Characterization of arcing fault in underground distribution cable. In: IPEC 2003- 6th International Power Engineering Conference.

Full text not available from this repository.

Abstract

Arcing fault detection has always been a difficult issue. This fault tends to be high fault impedance, the fault current is below maximum load limit and its detection is not possible through overcurrent relays. To study the characterization of arcing fault, an underground distribution system has been modelled and simulated using PSCAD/EMTDC program. An arc model is used to examine the diverse and complex characteristics of arcing fault. This paper presents some results in time domain and frequency domain. Results illustrated noticeable spikes and presence of DC component and second harmonic in arcing fault phase current, v.

Item Type:Conference or Workshop Item (Paper)
Uncontrolled Keywords:Arcing fault, harmonic analysis, PSCAD/EMTDC simulation, underground distribution cable