Ani, Farid Nasir and Badawi, E. M. and Kannan, K. S. (2005) The effect of absorber packing height on the performance of a hybrid liquid desiccant system. An International Journal Renewable Energy, 30 (15). pp. 2247-2256. ISSN 0960-1481
Full text not available from this repository.
Official URL: http://www.elsevier.com
Abstract
A hybrid system consisting of vapour compression unit, a liquid desiccant system, and a flat solar hot water collector were designed, fabricated and tested. This combination allowed for a separate control of humidity and temperature without energy penalty. Various packing heights of the absorber component were tested to determine the optimal performance of the combined unit. A 1000 mm packing height with cross-sectional area of 600×600 mm, proved to be the best height that gives promising improvements in the coefficient of performance of the vapour compression unit.
| Item Type: | Article |
|---|---|
| Uncontrolled Keywords: | Liquid desiccant; Packing material height; Absorber |
| Subjects: | T Technology > TJ Mechanical engineering and machinery |
| Divisions: | Mechanical Engineering |
| ID Code: | 7061 |
| Deposited By: | Mr Mohd Shukri Ramli |
| Deposited On: | 16 Dec 2008 12:31 |
| Last Modified: | 16 Dec 2008 12:31 |
Repository Staff Only: item control page