Universiti Teknologi Malaysia Institutional Repository

Study on the effectiveness of lightning rod tips in capturing lightning leaders

Sidik, Muhammad Abu Bakar and Ahmad, Hussein and Salam, Zainal and Buntat, Zolkafle and Ong, Lai Mun and Bashir, Nouruddeen and Nawawi, Zainuddin (2013) Study on the effectiveness of lightning rod tips in capturing lightning leaders. Electrical Engineering, 95 (4). pp. 367-381. ISSN 0948-7921

Full text not available from this repository.

Official URL: http://dx.doi.org/10.1007/s00202-012-0270-6

Abstract

This paper addresses the performance of various lightning rod tips: pointed, concave, blunt, flat and conical for lightning air terminal (LAT). To observe the behaviour of the various lightning rod tips, laboratory examination was conducted under two conditions, i.e. corona emission pattern under quasi-static electric field and lightning impulse testing - with and without pre-ionization. The data obtained from the corona emissions were correlated to the surface sharpness area of the tip. Using dimensional analysis, it can be concluded there is strong evidence that increased surface sharpness can lead to an increase in the corona discharge current. In addition, an impulse test was conducted to determine the performance of the LATs with different tip types and sizes. Using the individual and competitive test, it was found that the blunt LAT is the most recommended receptor.

Item Type:Article
Uncontrolled Keywords:electrostatic, impulse testing, lightning protection
Subjects:T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions:Electrical Engineering
ID Code:47556
Deposited By: Narimah Nawil
Deposited On:22 Jun 2015 05:56
Last Modified:05 Mar 2019 02:08

Repository Staff Only: item control page