Universiti Teknologi Malaysia Institutional Repository

Prediction of salt contamination on high voltage insulators in rainy season using regression technique

S. Ahmad, Ahmad and Ahmad, Hussein and Salam, Md. Abdus and Tamsir, T and Buntat, Z and Mustafa, M. W. (2000) Prediction of salt contamination on high voltage insulators in rainy season using regression technique. TENCON 2000. Proceedings , 3 . pp. 184-189.

[img] PDF
428kB

Abstract

The severity of contamination on the high voltage insulator surfaces is the significant factor in determining the level of outdoor insulation and in choosing the types of insulators. In the equatorial region, the most dangerous kind of contamination is salt contamination. A regression technique has been used to develop a modified equivalent salt deposit density (ESDD) mathematical model with respect to meteorological conditions. This model provides a useful way for predicting contamination level and for determining frequency of washing the insulators in a given contaminated area

Item Type:Article
Subjects:T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions:Electrical Engineering
ID Code:2178
Deposited By: Dr Zaharuddin Mohamed
Deposited On:01 Apr 2007 04:33
Last Modified:01 Jun 2010 03:01

Repository Staff Only: item control page